Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
E. Doors, slide drawers should not require more than 30 inches space into aisles to
use.
F. Four post framework shall allow for room ventilation air to freely enter and exit
enclosure. Doors, side panels, blanking panels and top panels shall be designed for
controlled front to rear air flow if provided.
Equipment Floor Loading
An individual framework loaded with equipment shall be designed and constructed to floor
load requirements of less than 560 kg/m
2
(114.7 lb./ft
2
) The floor loading for an equipment
framework is calculated by dividing the frame weight by the area of a rectangle bounded
by the extended frame sides and half of the front (3 ft -0 in. or 18 in) and half of the rear (
2 ft.-6 in. or 15 in.) aisles. The standard framework footprint to be used in AT&T
calculations would be 26 in. wide and 24” deep. For four post frameworks use footprint
dimension of framework and same front and rear aisle dimensions. Total weight of
equipment should include all cables that may be required in normal field installation.
Equipment Units
Equipment units:
A. Shall be designed so they are installed from the front and cabled from the rear of
equipment framework assemblies,
B. Shall incorporate the use of holes or closed slots in mounting hardware for attachment
to equipment framework mounting surfaces, and be designed for 23” nominal width
framework,
C. Shall accommodate mounting in equipment frameworks using the 1-3/4 x 23 inch
mounting hole pattern shown in Figure 11-1, and
D. Limited applications of products that will not permit rear access will require that
equipment be designed strictly for front access where cabling, maintenance and normal
service be performed from front only. These products shall be designed for front access
and indicated on form ESP-001 and/or ESP-002 , Engineering Data, Equipment
Locating Restrictions as YES, “Front Access Only” Only those products intended
for limited applications such as CEV installations, ETSI compliant products or other
AT&T authorized use shall be designed for front access.
Copyright ©2014, AT&T . All Rights Reserved.